MOBICON-REMOTE ELECTRONIC SDN BHD
19, Jalan PJS 3/59,
Taman Sri Manja,
46000 Petaling Jaya,
Selangor, Malaysia.
+603-7783 2257
+603-7783 4316

DEGSON - PCKK4-PE DIN RAIL TERMINAL BLOCK

Previous 113 / 400 Next

DEGSON - PCKK4-PE DIN RAIL TERMINAL BLOCK Din Rail Terminal Block Terminal Blocks Degson
Quantity
Add Quotation


 Item Data        
Test   standard
IEC/EN60947-7-1:2009 / UL1059        
Pitch                                     [mm] 6.2        
Poles 01P        
EN60947-7-1   Test data  VDE   certificate NO. 40024860        
Rated   voltage                              [V] /        
Rated   current                                [A] /        
Rated   connection capacity(solid/stranded) [mm2] 0.2~4        
Surge   voltage category/pollution degree/material group III/3/I        
Rated   impulse voltage                    [KV] 6        
Rated   torque                                 [N.m] 0.5        
UL1059Test   data UL File   Number E228872        
Use   group B C D    
Rated   voltage                              [V] / / /    
Rated   current                                [A] / / /    
Rated   connection capacity (solid/stranded) [AWG] 26-Oct        
Rated   torque                            [Lb.   in] 5.4        
General   data /        
Screw M3        
Inflammability   class V-0        
Ambient   temperature                        [℃] -40~+105        
Relative   humidity 5%-95%        
Inspection   standard MIL-STD-105E   II        
AQL 0.65        
Warranty 12   months        
Material   and plating /        
Housing PA66        
Screws Copper   alloy,Ni plated        
Contact Copper alloy,Tin plated        
Cage Copper   alloy,Ni plated        
Wire   connecting          
Recommended   stripping length 8.0mm;          
1.)For   solid wire, stripping wire to the appointed length, then tightening with   rated torque.        
2.)For   stranded wire: stripping wire to the appointed length, mating with corresponding   type of ferrule, then tightening with rated torque. 
Tightening   process should be steady, can’t use explosive force.          
1.)单股硬导线,剥好对应长度的导线后,用额定的扭力拧紧;          
For solid   wire, stripping wire to the appointed length, then tightening with rated torque.        
2.)多股柔性导线,剥好对应长度的导线后,可以直接连接或者配套使用对应标准规格的冷压端头,用额定的扭力拧紧;    
For stranded   wire: stripping wire to the appointed length, mating with corresponding type   of ferrule, then tightening with rated torque.
注意事项:扭力要平稳,不能使用爆发力;( Tightening   process should be steady, can’t use explosive force.)      

Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Attachment  
*only support gif, jpeg, jpg, png, pdf
Messages*  




 
You have 0 items in you cart. Would you like to checkout now?
0 items
Switch to Mobile Version
Subscribe Newsletter